Fire Suppression System for Data Center

burning_keyboard_medium

 

Fire suppression systems for server rooms and data centers are essential to the server room itself. A fire suppression system will automatically extinguish a fire without the need for human intervention. Fire suppression systems for data centers must be suitable for clean air environments, as server rooms and data centers are mostly occupied by personnel.

The designs standards for Fire suppression systems for server rooms and data centers are carried out with strict guidelines, as the fire suppression agents used can be dangerous if not designed correctly.

Fires within these types of environments are suppressed in two different ways:-

 

Method 1 – Inert gas fire suppression systems for server room and Data Centres – Reduce Oxygen

This method uses Argon/Nitrogen and sometimes a small element of CO2 to displace the oxygen in the server room. The basis of this method is to reduce the oxygen level to below 15%. By reducing oxygen to this level it will suppress a fire. The design must also consider the safety of personnel and keep oxygen levels to above 12%, this will be sufficient to maintain life within an oxygen depleted environment.

  1. Inert gas fire suppression systems will discharge its payload within 1 – 2 minutes.
  2. Will generally have more cylinders than chemical gases.
  3. Work with higher pressures, 200 Bar or 300 Bar
  4. Will require Pressure relief venting
  5. Common names of gases, ProInert, IG55, IG541, Argonite and INERGEN
inert_gas_fire_suppression_icon

Direct links to inert gases below:-

inergen_fire_suppression_icon-90x90
INERGEN fire suppression systems – IG541. This gas is a mix of 50 Argon, 42% Nitrogen and 8% CO2.
Reduces oxygen levels to between 12-14%
proinert_fire_suppression_icon-90x90
PROINERT fire suppression systems – Low pressure IG55. This gas is a mix of 50 Argon, 50% Nitrogen.
Reduces oxygen levels to between 12-14%
proinert_fire_suppression_icon-90x90
IG55 fire suppression systems. This gas is a mix of 50 Argon, 50%

Reduces oxygen levels to between 12-14%

 

Method 2 – Chemical/Synthetic gas fire suppression systems for server room and Data Centres – based on cooling

Most Chemical/Synthetic fire suppression agents have some form of cooling mechanism. These systems generally use less gas and do not significantly reduce oxygen levels. However, as any synthetic or chemical agent, high doses can be toxic, therefor correct designs are absolutely necessary.

  1. Inert gas fire suppression systems will discharge its payload within 1 – 2 minutes.
  2. Synthetic fire suppression systems will deliver its payload within 10 seconds.
  3. Will less cylinders and in some cases the cylinders are larger than inert gas cylinders
  4. Low pressures are used only 25 Bar and 42 Bar
  5. Will require pressure relief venting for both negative and positive pressures during discharge
  6. Common names for synthetic agents are FM200, Halon, Novec1230, Ecaro, HFC227ea and HFC125
synthetic_fire_suppression_icon

Direct links to inert gases below:-

fm200_fire_suppression_icon-90x90
FM200 fire suppression systems – HFC227ea. Concentration levels of 7.9% – 8.5%

:- Works by Reducing/Absorbing heat.

novec_fire_suppression_icon-90x90
Novec 1230 fire suppression systems – FK-5-1-12. Concentration levels of 5.3% – 5.6%

:- Works by Reducing/Absorbing heat.

sapphire_fire_suppression_icon-90x90
Sapphire fire suppression systems – FK-5-1-12. Concentration levels of 5.3% – 5.6%

:- Works by Reducing/Absorbing heat. also known as Novec 1230

A typical server room will require :-

fire_suppression_control_panel-90x90
Fire Suppression Control Panel

A Fire suppression control panel, this is generally made up of two to three fire zones, a gas release button, Auto and Manual key switch and built in batter backup (for power failures)

fire_suppression_optical_detector-90x90
Smoke Detection

A minimum of two smoke detectors, irrelative of the room size.

Smoke detectors must be located in all voids, i.e. room, ceiling and floor voids

fire_suppression_bells-90x90
Audible Alarms

Bells and Souders, these will indicate an audible alarm for fire which has been detected in the room and alarm warning of an imminent fire suppression gas release

Warning Signs:-

Warning signs on doors that you are about to enter a fire suppression controlled area
Warning signs showing manual gas release points

Pressure relief

Pressure relief venting to compensate for both negative and positive pressures during a gas discharge.

More Information on fire suppression systems below:-